Parameter Permitted values Default values Range Description
Operating mode
  • Permanently open
  • Permanently closed
  • Overtemperature NC
  • Overtemperature NO
  • Undertemperature NC
  • Undertemperature NO
Overtemperature NO
  • Permanently open (deactivated) Fixed value independent of the measured temperature. The relay is open.
  • Permanently closed (deactivated) Fixed value independent of the measured temperature. The relay is closed.
  • Overtemperature NC If the alarm temperature is exceeded the relay will open.
  • Overtemperature NO If the alarm temperature is exceeded the relay will close.
  • Undertemperature NC If the temperature falls below the alarm temperature, the relay will open.
  • Undertemperature NO If the temperature falls below the alarm temperature, the relay will close.
Switching threshold 0 °C…70 °C 45 °C 1 K If the parameterised switching threshold value is exceeded, an action depending on the operating mode will be triggered.
Hysteresis 0 K…-10 K -5 K 1 K If the temperature has dropped about the set hysteresis the action will be switched off.

Example:
Operating mode Permanently closed
Switching threshold 50°C
Hysteresis -10 K
At 51 °C the relay stays closed.
At 41°C the relay also stays closed.
The external air conditioning unit will not be controlled. The relay is deactivated.